Appendix N
Shakespeare Fiberglass Pole Testing
Georgia Power Company Research Center
Project # C93748
March 1994
Introduction
Mr. John Lewis of Shakespeare Company contracted with Georgia
Power Company Research Center / Southern Electric International to
perform critical impulse flashover tests on a CCA pole and a fiberglass
pole. In addition to
these tests, 12 - 2" X 18" samples of fiberglass pole were tested for
QUV exposure, resistive leakage, and critical impulse flashover values.
Pole Configuration Impulse Flashover Tests
Critical Impulse Flashover Tests were performed on a CCA and a
fiberglass pole, Both poles were connected in the configuration shown
in Appendix (N)A.
In order to determine the critical impulse flashover values, impulses
were applied to each test configuration using the up-down method
described
in ANSI/IEEE Std. 4 - 1978. The average value of these flashovers was
computed and the voltages were corrected to standard atmospheric
conditions using ANSI C29.1 voltage corrections. Each configuration was
tested under wet and
dry conditions. The water spray pattern used in the test was the IEEE
Std.
4
- 1978 Revised Wet Test. The critical impulse flashover values are
given in Table 1. The flashover values can be used to obtain Basic
Impulse
Level values for insulation materials. The BIL value for a particular
insulation material is the level of voltage which the insulation
material should be able to withstand without a disruptive discharge.
For this reason, critical
impulse flashover values are higher than stated BIL values for an
insulation
material.
ANSI Standard C29 uses approximately 90% of the critical impulse
flashover
value as the BIL value for an insulator. This value could be used as
the BIL value to choose for these poles. During the flashover tests
both
poles experienced the splitting of the fibers on the external surface
of the
poles.
This splitting exposes the internal portions of the pole to weathering.
After the third impulse application, the frayed fibers on the pole's
surface
caught on fire. The flames were extinguished in order to minimize
damage to
the pole's surface while determining the flashover values. Each
consecutive
flashover
produced some burning of the fibers. The flames required extinguishing
approximately
4 times. Photographs of the CCA and fiberglass poles are shown in
Appendix
(N)B.
|
Critical Impulse Flashover Values |
|||||
|
Polarity |
Flashover Values (kV) |
Flashover Values (kV) |
|||
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fiberglass Pole Section Tests
Twenty-four 2" X 18" pole samples were received for testing. These samples were divided into two groups. Twelve were placed in storage and twelve were placed in QUV and condensation aging. The samples were cycled between QUV @ 60 degrees C every 4 hours for 1036 hours. A data sheet describing this test is included in Appendix (N)C.
After the QUV/Condensation aging tests were completed, three samples from each test group were soaked in tap water for three days. Following this soak period, three more samples were taken from the two dry test groups for comparison against these soaked samples. Two comparison tests were performed.
The first of these comparison tests was an ac
resistive leakage current test. This test measures the effect of
moisture absorbed during
the soak test. Any moisture absorption in the test samples will produce
increased
resistive leakage current. Because the test is an ac voltage test, even
moisture
which does not extend for end to end in the test samples can be
detected.
The results of these tests are shown in Table 2.
|
93-732 C93748 Shakespeare Fiberglass Pole Samples High Voltage AC Resistive Current Measurements |
||
|
|
(µA) |
(W) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
93-732 C93748 Shakespeare Fiberglass Pole Samples Critical Impulse Flashover on 2" X 18" Samples |
|
|
|
(kV) |
|
|
|
|
|
|
|
|
|
|
|
|
Conclusions
The test data from the pole configuration impulse flashover test shows only slight variations between the flashover values for the fiberglass and CCA poles. However, under wet conditions, the CCA pole displayed a lower flashover value than the fiberglass for this configuration. Typical BIL values for distribution systems are much below the flashover values for these configurations. Therefore, it is likely the transformers, lightning arresters, and switches on the system may limit the voltages on the lines to less than these flashover values for induced lightning surges. During these flashover tests, some burning of the frayed fibers on the fiberglass pole was observed. For this reason, a comparison of the power arc flashover recovery of both poles may be desired.
The data from the fiberglass pole sections
indicates those samples which were exposed to QUV aging have become
more resistant to
moisture pickup than the new samples. One possible explanation for the
reaction
could be the QUV light and heat in the test equipment has helped to
cure
the paint and resin materials. The malleability observed in the
coatings
during mounting supports this conclusion. The increased resistive
leakage
for the water soaked control samples indicates these samples absorbed
more
water than the QUV aged samples. The effect of this moisture pickup on
the
impulse flashover value is based on the pattern in which the moisture
entered
the samples. In most cases, moisture absorption decreases the flashover
of
the test sample. This decrease in flashover value is caused by an
uneven moisture
distribution which results in a non-uniform electric field. This
non-uniform
field distribution allows the plasma arc to initiate more easily, thus
resulting
in a low flashover value. The flashover value for those samples which
picked
up moisture in this test displayed these characteristics. The soaked
control
samples had the lowest flashover value, -263.6 kV lower than the soaked
QUV
samples. The flashover of the dry samples was almost 60 kV higher than
the
soaked control. Therefore, the moisture is definitely decreasing the
withstand
capability. The difference between the dry control and dry QUV samples
was
only 2.3 kV and should be considered insignificant.